Error processing SSI file
Catalog Request


INTERFACING ABSOLUTE POSITION DECODERS
TO PLCs AND MICROCOMPUTERS
 

Microcomputers and PLCs are sequential logic devices.  In contrast to a real-time hardware logic, which can perform many operations at the same time, a PLC can perform only a single operation before proceeding to the next logical step.  The figure describes the logical operation of a PLC, which is cyclic in nature.  During the I/O scan, the PLC looks at the input data
available at the input terminals and activates the outputs based on the ladder logic.  During the processor scan, the new input data is processed by the Central Process Unit (CPU) according to the ladder program and the outputs are updated during the next I/O scan.  This cycle repeats again and again

The expression "garbage in, garbage out" fits very well to the PLC.  If the input data is invalid or incorrect, the corresponding machine operation also be incorrect.  Therefore, it is very important that when the PLC reads the decoder input during the I/O scan, the decoder data is valid and free of any ambiguities.

There are two main inherent characteristics of electronic devices that could cause wrong decoder data into the PLC:

a)  PLC Reading the Changing Bit Pattern:
As we all know, a BCD, binary, or gray code number is composed of various bits that change state when decoder position passes from one number to the next.  Inherently, in Gray Code only 1 bit changes state when changing from one number to the next, while in BCD or Binary data more than on bit may change for each number change.  Let us consider the example of changing decoder position from 199° to 200°.

In a BCD code, for this 1° change of position, 6 bits will change state, i.e., 100, 80, 10, 8, and 1 bit will go LOW and 200 bit will go HIGH.  And, due to the reaction time of electronic components, all these bits do not change state at the same time.  At a given time when PLC reads the data, some bits might have gone LOW while others may still be HIGH.  Therefore, while reading the above changing bit pattern the PLC is liable to read a wrong number.

b)  Reaction Time of PLC Input Modules:
PLC I/O modules, even the TTL compatible ones, have lengthy and inconsistent time delays when they change their logic state.  This inconsistency gets further compounded by long wiring runs between the decoder and the PLC, and also the limited current drive capability of the decoder outputs.  In the above example, when the input to the I/O module goes from 199° to 200°, the output may stay at 000 for a time, depending on the I/O module reaction time.


An  I/O scan during this time (2 to 10 ms in typical installations) will read false data to the PLC.  The solid line is the field side of the I/O module and the dashed line the PLC side.  During the switching time (TS), the decoder information as seen on the PLC side is 0, which is invalid.

Even dedicated microprocessor controls with faster scan times are faced with the above two problems, though to a lesser degree.  In microprocessors the TS is in microseconds instead of milliseconds and software can be designed to ignore inconsistent data.  If your microprocessor does not have this software provision or in you are using a PLC, the hardware synchronization described below must be used to assure the integrity of the incoming decoder data.

 

Page 2

 

Error processing SSI file