INTERFACING ABSOLUTE
POSITION ENCODERS TO PLCs & MICROCOMPUTERS
PLC
Synchronization (PC-Handshake):
Whenever
the PLC scans the encoder input, it must see stable data. In
order to ensure this, the PLC gives a data transfer command and a
predetermined time later the PLC synch circuit stabilizes the data
for the PLC to read. This time is adjustable on some AVG
Automation units (2 µs to 30 ms), where as it is fixed on others
(50 µs, 100 µs, etc.). The variable time feature, when
available, can be used to provide the most fresh data to the PLC.
For
example, the time interval between the data transfer and read
commands might be 12 ms and say the time delay is set at 5
ms. After 5 ms of the data transfer command the stable data
is available to the input modules of the PLC and when the PLC
commands the data to be read 12 ms later, it is stable and valid.
|
|
Page 3 |